www.wondoor.com

Won-Door FireGuard™ 20, 60, 90, 180 Specifications
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors

PART 1 - GENERAL

1.01 SUMMARY OF WORK
A. Division 0 and Division 1, as indexed, apply to this section.
B. Furnish and install all horizontal sliding, accordion-type fire doors shown on the drawings and specified herein.

1.02 RELATED SECTIONS
A. All headers, support structures, surrounding insulation, jambs, storage pockets, pocket doors, access doors, blocking and trim shall be furnished and installed by other sections.
(Note: Plywood headers may be included under options. See 2.04 Option K. The plywood header option does not include support structures, surrounding insulation, jambs, storage pockets, pocket doors, access doors, blocking, drywall work or trim.)
B. All electrical wire, wiring, conduit and electrical boxes shall be furnished and installed by electrical section.
[C. All track, soffit, chain guide and wall mounted striker posts shall be painted by Section 09900. Color shall be selected by the architect.]
[D. (Note: The following paragraph should be included when 2.04 Option T, ASL-Advanced Synchronized Locking, is specified)
Regarding 2.04 Option R – The Microsoft Windows based PC shall be supplied by the owner. Wiring from the computer to the doors shall be furnished and installed by the electrical section and shall consist of one (1) USOC RJ14-6POS 4 wire jack per line, up to eight (8) lines, installed near the computer. From the computer, each line shall daisy chain up to 32 doors together with one (1) USOC RJ14-6POS 4 wire jack installed on the back wall of the storage pocket for each door. Wire used in the daisy chain shall be a minimum of CAT 3 twisted 2 pair cable. Each line shall be 4000 feet or less in length.]
[E. (Note: The following paragraph should be included when 2.04 Option N, individual LCD door status display panel, is specified)
Regarding 2.04 Option M – One (1) USOC RJ14-6POS 4 wire jack shall be supplied at the back of the storage pocket and shall be tied to the 4 square junction box adjacent to the door with CAT 3 twisted 2 pair cable. The junction box, RJ14 jack and wire shall be furnished and installed by the electrical section. Termination to the LCD panel shall be by punch down block and shall be by the electrical section as per the manufacturer’s instructions. If the LCD panel is supplied with Option N, Then the CAT 3 twisted 2 pair cable can be terminated in parallel with the ASL wiring in the same USOC RJ14-6POS 4 wire jack.]

1.03 QUALITY ASSURANCE
A. Installation shall be performed by factory trained and certified installers with a minimum of three years experience installing accordion-type fire doors.
B. Fire doors shall be listed by Underwriters Laboratories for ratings as indicated, when tested in accordance with the requirements of UL 10B and ASTM E-2074.
C. Automatic closing system shall be listed by Underwriters Laboratories in accordance with the requirements of UL 864.
D. Fire doors used for smoke and draft control shall bear the “S” mark on the fire door label and shall have an air leakage of less than 3 ft3/ft2 at 0.1 inch of water column pressure when tested in accordance with UL 1784 with an artificial bottom seal.
E. Fire doors used at the point of access to an elevator shall bear the “S” mark on the fire door label and shall have an air leakage of less than 3 ft3/ft2 at 0.1 inch of water column pressure when tested in accordance with UL 1784 without and artificial bottom seal.

1.04 SUBMITTALS
A. Refer to Section 01300 - Shop Drawings and Submittals.
B. Indicate required stacking depth, storage pocket width and height of header above finished floor. Show installation details, layout, and electrical requirements.

1.05 DELIVERY, STORAGE, AND HANDLING
A. Deliver to the job site in manufacturer's original, unopened package.

1.06 COORDINATION BY GENERAL CONTRACTOR
A. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation of header, jamb, and trim. Provide field dimensions for fabrication. Supervise unloading and handling of materials.
B. Permanent power shall be in-place and ready for final connection when fire doors are erected. Assure access to and proper clearance for motor operators.
C. After testing the fire alarm system, automatic-closing fire doors shall be re-set to the original positions.
D. Store boxes flat (not more than three high) in a dry area and protect from elements that may damage materials. Replace damaged materials at no cost to the owner.

1.07 WARRANTY
A. Materials and installation shall be warranted against defects in workmanship for a period of one (1) year from the date of substantial completion.
[B. A Manufacturers Service Agreement shall cover years 2 thru 5 and include regularly scheduled testing and inspection of all door functions. The Service Agreement will include (select one: annual, semi-annual, quarterly or monthly) visits to inspect, test and perform all required maintenance. All service and maintenance functions are performed by factory-trained, service technicians.]
[C. A comprehensive owner training seminar will be conducted by a factory trained, service technician. The owner training shall include horizontal sliding, accordion-type fire door operation, care, maintenance, testing and trouble-shooting.]

PART 2 - PRODUCTS

2.01 MANUFACTURER AND MODEL
A. Horizontal sliding accordion-type fire doors shall be Won-Door FireGuard model FG [select one: 20, 60, 90, or 180] (number designates minutes of fire rating) as manufactured by Won-Door Corporation, Salt Lake City, Utah. (Note: Add suffix “S” for standard doors OR suffix “E” if door is used at the point of access to an elevator OR suffix “TR” for temperature rise of 450? F at 30 minutes. When specifying “TR” doors, contact the manufacturer for pocket depths, hanging weight and size limitations.)
B. Products of other manufacturers demonstrating complete compliance with each of the fire rating and performance criteria of the product specified will be considered for approval. Written requests for substitutions will be considered by the architect up to ten days prior to the bid date.
[C. No substitutions allowed.]

2.02 FIRE RATING
A. Fire Doors shall be listed by Underwriters Laboratory as special purpose fire doors having a [select one: 20, 60, 90, or 180] minute fire-resistive rating in accordance with the requirements of UL 10B and ASTM E-2074.

2.03 REMOTE MONITORING AND CONTROL
(Note: Remote Monitoring and Control may be specified under 2.04 Option T)
A. Fire doors shall be capable of being remotely monitored and controlled by a personal computer (PC). Information displayed on the computer shall indicate the voltage of the battery, AC line voltage and error conditions. Status information shall indicate whether the door(s) is closed, open, closing, opening, stopped, blocked or locked. Access using the Fire Exit Hardware shall be indicated as well as when the door(s) has received a fire signal.

2.04 MATERIALS
A. Construction: shall consist of two parallel, accordion-type walls of panels independently suspended with no floor tracks, pantographs, or interconnections except at the lead-post.
B. Panels shall be formed of 24-gauge enamel coated steel V-grooved for strength and resilience. Panels shall be connected by full height 24-gauge enamel coated steel hinges. Panels shall be modular in design and capable of in-place repair-ability.
C. Suspension System: shall consist of two 14-gauge cold rolled steel (or .125 aluminum) tracks on 8" (.203) centers attached to the overhead structural support. Each lead post shall be suspended by an 8-wheel ball bearing trolley. Each panel shall be suspended by a steel hanger pin and a ball bearing roller.
D. Lead-posts: shall be of 24-gauge cold rolled steel and shall be connected by specially formed steel panels. An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignment during operation and insure a tight fitting closure.
E. Perimeter Seals: shall consist of continuous extruded vinyl sweeps attached to the top and bottom of the fire door to form a smoke and draft seal.
F. Hanging weight shall be 5.5 pounds per square foot.
G. Automatic Closing System shall consist of the following:
1. Microprocessor based Electronic Control box with these features:
a. Ability to monitor dual power sources continually for peak performance including:
1. Detect a missing battery, bad battery, or low battery condition.
2. Detect if the charging circuit is bad.
3. Detect fuse failures.
4. Detect high or low AC conditions.
b. Ability to monitor the health of the drive train including:
1. Direction errors, obstruction errors, hindrance errors, and position errors.
2. Active daily path checks, by actually closing and opening to assure a clear path and proper operation.
3. Ability to monitor a passive input such as an infrared light beam to assure the closing path is clear.
c. Ability to monitor inputs including:
1. Sticky door block, exit hardware, patron hardware, and key switches.
2. Key switch mis-wires where key open and key close are both on simultaneously.
d. Ability to self-monitor the health of:
1. Internal volatile and non-volatile memory.
2. Proper operation of firmware.
e. Ability to run a “watch dog” monitoring circuit which will force a software restart in the event the software hangs, including the ability to track the number of resets that occur for diagnostic purposes.
f. Ability to record the number of times the door has closed, opened, lost communication with external microprocessors, and the number of times the controller has been reset manually.
g. Ability to monitor ambient temperature and lockout the operating devices once the environment at the door becomes untenable.
h. Ability to enter a security mode to help control access through the door including:
1. The ability to automatically re-close and secure itself after a legitimate patron access has occurred.
2. The ability to unlock and revert to a fire door in a fire alarm condition, including the ability to re-lock automatically after the fire alarm condition has cleared.
i. Ability to withstand voltages up to 120 volts AC on the fire alarm input circuit without damage including the ability to indicate that the alarm circuit has not been wired as a dry contact, “no voltage” circuit when errant voltages are applied to the circuit.
j. Ability to communicate with other microprocessors on the system via an internal bus system, including but not limited to microprocessors on the motor drive, in the leading edge of the door, and on a wall mounted display panel adjacent to the door.
k. Ability to indicate trouble or supervised information both locally and at a remote location. Communication to the remote location shall be by either relay logic or digital data streams to our proprietary ASL system (see options).
2. Motor Operator Assembly including:
a. A DC gear-motor, drive sprocket, clutch, and position sensors. The motor shall drive the fire door by means of a chain attached to a stabilizer bar trolley each time the door operates including the initial closing cycle.
3. A door control momentary rocker switch shall be mounted on one side of the door near the lead post and shall have the following functions: Pressing the upper portion of the switch shall close the door and/or clear fault conditions. Pressing the lower portion of the switch shall open the door and/or temporarily mute the local horn. For doors using wall mounted key switches, option L, a color coordinated cover plate shall be provided to fill the hole left when the rocker switch is removed.
4. The control box shall be equipped with a service switch that performs the following functions:
a. When the switch is off with AC power present, the controller shall emit an audible coded sound indicating the system is out of service. In this mode all normal functions shall cease including motor and communications.
b. When the switch is off and AC power is not present, the controller shall enter a sleep mode during which the system shall use the battery to monitor the AC line for power but do nothing else.
c. When the switch is moved from the off position to the on position, the controller shall enter a calibrate mode where it emits a coded audible alert indicating that the door needs to be closed to complete the calibration sequence. As soon as the door is closed, the controller shall automatically stop the audible alert, and resume all normal functions and monitoring.
H. Leading Edge Obstruction Detector:
1. Shall be pressure sensitive such that each contact with an obstruction shall cause the door to stop, reverse enough to remove pressure on the leading edge, pause, and then re-close when in an alarm condition. The leading edge obstruction detector shall be fully functional at all times, including during the initial closing cycle.
2. Constant pressure to the leading edge in the direction of opening shall, while the door is opening under motor power, continue to open under motor power until the leading edge is released. This is termed motor assisted opening.
3. Constant pressure to the leading edge while not under motor power shall prevent motor operation and allow the door to be opened manually.
I. Exit Hardware shall be located on both sides of each fire door.
1. In emergency mode, a slight pressure on the hardware will cause the door to open a minimum of 32 inches, pause for 3 seconds, and then automatically close.
2. The open distance shall be field programmable, up to the entire opening width, if the local authority requires an opening larger than 32 inches.
3. The pause before re-close shall be field programmable, up to 30 seconds, if the local authority requires a longer pause time.
4. The exit hardware shall have the ability when not in the emergency (fire) mode or the security (lock) mode to be used to open the door and move it back into the storage pocket.
5. The exit hardware shall be field programmable to provide access control. When programmed, the exit hardware shall not respond when pressed until activated by signal from smoke detector or fire alarm.
J. Suffix “E” doors shall include the following extras; track seals, anti-sway brackets every five feet or less across the opening, modified lead post trolleys and on “S” doors foil tape between the panels and the smoke liner.

OPTIONS
[[K. Plywood headers shall be provided. Installation is contingent on the structural support being less than five (5) feet above the plywood header assembly. Materials included are the plywood, threaded rods, and mechanical attachment hardware only. Drilling/placement of anchorage points into pre- or post-tensioned decks is by others. Welding/punching/drilling of steel members is by others. All drywall work is by others. Field dimensions are included.
[L. Vision Panel shall consist of frame and clear glass assembly with listings from Underwriters Laboratory up to 1 1/2 hours]. (Note: required only in smoke barriers in Group I occupancies.)
[M. A Key switch module shall be provided.] (Note: required for doors with Large Door Motor Operators and doors equipped with Access Control devices.)
[N. An individual LCD door status display panel shall be provided adjacent to the door to indicate in the English language the status of the door, i.e. door position and trouble conditions. It shall have a port that allows easy access to a diagnostic tool for the purposes of field programming the door to customized settings. When used with the ASL system, it shall be compatible and not disrupt the ASL communications] (Note: Electrical requirements for the LCD panel can be found in 1.02 E Related Sections)
[O. Air Pressure Resistance. (Note: This option should be specified for applications where the fire door will be subjected to air pressure differential of up to .15 inches of water column) The door shall be capable of resisting an air pressure differential to .15 inches water column and maintain normal operation. Anti-Sway Brackets shall be placed interior to the door approximately every five feet or less. Self-Leveling lead post assembly shall provide motorized tracking of the leading edge of the door to assure proper closure.
[P. An infrared light beam shall be provided on non-curved doors to monitor the opening path. In the event that an object is placed in the path of the door for more than 4 minutes, the beam shall cause the door to sound an alarm indicating a path obstruction.]
[Q. Acoustic Insulation: Interior surfaces of both walls shall be completely covered with a continuous blanket of 2 lb. density foil-backed fiberglass fastened in place with steel spring-clips]. (Note: When specifying insulated doors, contact the manufacturer for pocket depths, hanging weight and size limitations.)

OPTIONS - ACCESS CONTROL/MONITORING
(Note: Level 1 and Level 2 Access Control options are independent systems and may not be specified in conjunction with each other)
[R. Level 1 Access Control. The Exit Hardware shall not respond when pressed until activated by signal from smoke detector or fire alarm. Upgrades to the fire door for this level of access control shall include a heavy-gauge steel sliding jamb and rigid jamb stops.] (Note: at least one key-switch required.)
[S. Level 2 Access Control. An Electromagnetic lock shall be added to the motor operator assembly to provide 400-500 pounds of resistance to manual opening until activated by a signal from fire alarm. When the fire alarm is cleared, the door returns to normal access control. Upgrades to the fire door for this level of access control shall include a heavy-gauge steel sliding jamb, rigid jamb stops and 10-guage steel vertical reinforcement to the lead post.] (Note: at least one key-switch required.)
[T. The Advanced Synchronized Locking (ASL) system, as manufactured by Won-Door Corporation, shall be furnished and installed to continuously control and monitor the status of up to 256 doors. ASL shall consist of a Multi-port On-site Monitor box, a serial cable, a 12-volt power supply and software on CD-ROM media. Installation, jacks, a computer (PC) and wiring shall be provided by others.] (Note: Electrical requirements for the ASL system can be found in 1.02 D Related Sections)

2.05 COLOR
Color shall be manufacturer’s standard #55 Platinum.
[Color shall be selected from manufacturer's optional colors at additional cost.]
[Color shall be selected by architect and field painted by others.]

PART 3. EXECUTION

3.01 PREPARATION BY GENERAL CONTRACTOR
A. Openings shall be to the dimensions specified, plumb and level.
B. Headers shall be parallel with the finished floor within +/- 1/8” tolerance over the entire length of the opening.
C. Manufacturer shall make available to the General Contractor a video showing door opening preparation.

3.02 INSPECTION
A. Inspect openings prepared for fire doors and surrounding conditions. Immediately notify the architect, in writing, of any unacceptable conditions.

3.03 INSTALLATION
A. Install fire doors in accordance with manufacturer's instructions for clearance and fastenings.
B. Adjust for smooth, quiet operation. Verify that all operations are functional and meet the requirements of applicable codes and regulations.
C. Upon completion of the installation, general contractor shall protect fire doors from damage and shall replace or repair subsequent damage so that doors are acceptable to the architect at no additional cost to the owner.
D. Installation shall be performed by factory trained and certified installers with a minimum of three years experience installing accordion-type fire doors.

3.04 DEMONSTRATION
A Manufacturer’s onsite field technician shall demonstrate the operation of the doors to the General Contractor. A video outlining the operation of the door, scheduled maintenance, basic troubleshooting and care of the door system shall be provided to the owner by the door manufacturer.

Copyright © 2006 by Won-Door Corporation, all rights reserved.